Dedicated compartments for LPG cylinders and regulators

Cylinder compartments are dedicated compartments that should only house the cylinders and associated gas equipment. Doors should be fully sealed, lockable and clearly labelled.

Compartment doors should have upper and lower ventilation to allow leaking gas to escape, or there should be a drain hole within the compartment. The drain hole can have a hose attached to it to move leaking gas away to a safe location.

  • The drain hose for the compartment must terminate at least 1500mm away from an ignition source
  • Any opening - vents or drains - must be located outside of the 1500mm ignition zone.

Typical LG Gas lockers and cylinder compartments have vents in the top and bottom of the compartment opening. Both vents must be a minimum of 5000mm2 and the bottom vent must be 25 mm2 from the base. The drains must be at the rear or bottom of the compartment and be a minimum of 500mm2


Page last updated 8 February 2024

Provided by:
Department of Energy and Mining
URL:
https://www.sa.gov.au/topics/energy-and-environment/safe-energy-use/festivals-events/lpg-cylinders-and-ignition-sources/dedicated-compartments-for-lpg-cylinders-and-regulators
Last Updated:
08/02/24
Printed on:
16/05/24
Copyright statement:
SA.GOV.AU is licensed under a Creative Commons Attribution 4.0 Licence. © Copyright 2024
Close